RWB-200 digital microcomputer protection device is suitable for low current/small resistance grounding system of 35kV and below, which integrates functions of protection、control、communication and monitor. The device uses component programmable design ideas to reduce maintenance workload and spare parts. It can flexibly meet the needs of a variety of applications, and is the ideal replacement production for traditional electromagnetic relay protection.
|
Function |
RWB-200 |
|
|
Configuration |
Digital input |
8 channel passive |
|
Relay output |
4 channel passive |
|
|
AC voltage input |
4 channel |
|
|
AC current input |
4 channel |
|
|
Protection |
Over current I protection |
n |
|
Over current II protection |
n |
|
|
Over current III protection |
n |
|
|
Time inverse current protection |
n |
|
|
Overload Protection |
n |
|
|
Zero sequence current protection |
n |
|
|
Negative sequence current protection |
n |
|
|
Low voltage protection |
n |
|
|
Over voltage protection |
n |
|
|
Loss voltage protection |
n |
|
|
Zero sequence voltage protection |
n |
|
|
Negative sequence voltage protection |
n |
|
|
Reclose protection |
n |
|
|
Post acceleration protection |
n |
|
|
Automatic Transfer Switch [Automatic backup power supply] |
n |
|
|
Motor startup over current protection |
n |
|
|
Motor overheating protection |
n |
|
|
Motor long startup time protection |
n |
|
|
Non-electricity protection(4 channel) |
n |
|
|
Monitoring |
Switching monitoring |
n |
|
Abnormal alarm: CT breaking |
|
|
|
Abnormal alarm: PT breaking |
n |
|
|
Abnormal alarm: control loop breaking |
|
|
|
Event record |
n |
|
|
Fault Wave ecording |
|
|
|
Control |
Anti-jump circuit |
|
|
Communication |
RS485 |
n |
|
|
|
|
Normal temperature: -10℃~55℃
Limited temperature: -30℃~70℃
Storage temperature: -40℃~85℃
Relative humidity: ≦95% No Condensation
Atmospheric pressure: 80Kpa~110Kpa
Power Supply: AC/DC 85~265V ;DC48V
AC Rated data : Current 5A、1A
Voltage 100V
Frequency 50HZ
AC current loop Ie=5A no more than 0.5VA per phase
AC volgate loop U=100V no more than 0.5VA per phase
DC power supply loop normal operation is not greater than5W
Protection action is not greater than5W
AC current loop 2Ie Continuously working
10Ie Allow work 10S
40Ie Allow work 1S
AC volgate loop 1.2Ue Continuously working
power supply loop 80%~110% Rated Voltage Continuously working
AC input to ground is greater than 500 megohms
DC input to ground is greater than 500 megohms
Signal and output to ground greater than 500 megohms
Digital input to ground greater than 500 megohms
Between each loop is greater than 500 megohms
Can withstand 2KV, lasting 1 minute of power frequency withstand voltage and 5KV surge voltage
1 The high-performance 32-bit processor provides powerful computing processing, profect circuit design, and industrial-level components to ensure stable and reliable operation.
2 Unique component level - engineering level - user level,three level programming mode, component type can be set on site. The digital input and relay output are programmable.
3 High-speed and high-precision AC signal measurement with sampling frequency up to 1600Hz. Multiple channels AC signal FFT calculations are done in milliseconds. Sampling values are digitally corrected and can effectively suppress noise and offset.
4 A powerful vectorization calculation algorithm can obtain a variety of derived AC signal characteristics, including positive, negative, zero sequence, phase-to-line transformation, angle, impedance, power and so on.
5 The device is capable of continuously recording 64 events, with a full event record of the protection action with fault time, type, and peak value.
6 Graphic LCD(128x64), can display graphics, icons and full English&chinese display.
7 The main signal process circuit is equipped with an electromagnetic interference absorbing element to meet the working environment in a harsh electromagnetic environment.
8 The enhanced MODBUS-RTU communication interface can transmit real-time waveforms, vector data, etc. in addition to normal data.
9 Complete self-test function, including tuning parameters, recording, operation loop, current, voltage loop and other abnormal monitoring.
10 The fully enclosed thin metal chassis is waterproof and dustproof, and has strong anti-static and electromagnetic interference capability; it can be installed on the switch cabinet in a distributed manner, and can also be grouped.
11 SMT technology, important components (such as power supply modules, transformers, relays, LCDs, terminals, etc) adopt mature products from well-known enterprises at inboard and abroad to ensure that the average running time more than 100,000 hours.