RWB-301Microcomputer integratedprotection device

The digital microcomputer protection device is applicable to the small current/small resistance grounding system of 35kV and below, integrating
protection, control.communication, monitoring and other functions. The device uses the idea of component programmable design to reduce the maintenance workload and spare parts, which can fexibly meet the needs of a variety of applications, and is the most ideal substitute for traditional electromagnetic relay protection.

→ Download Catalog

Contact Us Category Digital Protection Relay
  • Product Details
  • Main function configuration
  • Technical Parameters
  • Main features
The digital microcomputer protection device is applicable to the small current/small resistance grounding system of 35kV and below, integrating 
 protection, control.communication, monitoring and other functions. The device uses the idea of component programmable design to reduce the maintenance workload and spare parts, which can fexibly meet the needs of a variety of applications, and is the most ideal substitute for  traditional electromagnetic relay protection.
Functional items Comprehensive
To configure Switch input 10 passive
Relay output 5-way dry contact
AC current input 4-way
AC voltage input 4-way
Protect Current quick break protection
Time limited quick break protection
Over current protection
General inverse time overcurrent protection
Overload protection
Zero sequence current protection
Negative sequence current protection
Low voltage
Overvoltage protection
Loss of voltage protection
Zero sequence voltage protection
Negative sequence voltage protection
Reclosing protection
Rear acceleration protection
Standby automatic switching protection
Motor starting overcurrent protection
Overheating protection
Protection against excessive startup time
Non electric quantity protection(6 circuits)
Monitor Switching value monitoring
Abnormal alarm:CT disconnection
Abnormal alarm:PT disconnection
Event record
Signal communication Communication(RS485,modbus protocol)

1 Environmental conditions

Normal temperature:     -10℃~55℃ 

Limited temperature:    -30℃~70℃ 

Storage temperature:    -40℃~85℃ 

Relative humidity:         ≦95%  No Condensation 

Atmospheric pressure:    80Kpa~110Kpa

2 Rated data

Power Supply   AC/DC 85~265V ;DC48V

AC Rated data :   Current 5A、1A

                                 Voltage 100V

                                Frequency 50HZ

3 Power consumption

AC current loop        Ie=5A          no more than 0.5VA per phase

AC volgate loop        U=100V        no more than 0.5VA per phase

DC power supply loop        normal operation is not greater than5W

Protection action is not greater than5W

4 Overload capability

AC current loop         2Ie                       Continuously working

                                   10Ie                      Allow work 10S

                                   40Ie                      Allow work 1S

AC volgate loop        1.2Ue                     Continuously working

power supply loop      80%~110% Rated Voltage     Continuously working

Insulation & Withstand voltage performance

AC input to ground is greater than 500 megohms

DC input to ground is greater than 500 megohms

Signal and output to ground greater than 500 megohms

Digital input to ground greater than 500 megohms

Between each loop is greater than 500 megohms

       Can withstand 2KV, lasting 1 minute of power frequency withstand voltage and 5KV surge voltage

☆High performance 32-bit processor is used to provide powerful computing and processing capacity,circuit design is refined,and industrial    grade components are equipped to ensure stable and reliable operation of the device.

☆Unique three-level programming mode of element level-engineering level-user level,and element type can be set on site.Switch input and relay output are programmable.

☆High speed,high-precision AC signal measurement,sampling frequency up to 1600Hz.The FFT calcuation of multiple AC signals is completed   in milliseconds.The sampling value is digitally corrected,and the noise and offset can be ffectively suppressed.

☆Powerful vectorization calculation method can obtain a variety of derived AC signal characteristics,including positive,negative,zero sequence,phase line transformation,angle,impedance,power,etc.

☆63 events can be recorded continuously,with full event record of protection action of fault time,type and peak value.

☆Graphic LCD(128×64),graphics,icons and full Chinese display.

☆The main signal circuit is equipped with electromagnetic interference absorbing elements,which can meet the working environment under   harsh electromagnetic environment

☆Enhanced MODBUS communication interface can transmit real-time waveform,vector data,etc.in addition to normal data.

☆Perfect self inspection function,including setting parameters,recording,operation circuit,current,voltage circuit and other abnormal   monitorng.

☆Fully enclosed thin metal case,waterproof and dust-proof,with strong anti-static and electromagnetic interference capabilities; it can be installed locally on the switch cabinet in a distributed way,or it can be assembled into panels in a centralized way.

☆Surface mounting process,important components(such as power module,transformer,relay,LCD,terminal,etc.)The mature products of 

well-known enterprises at home and abroad are used to ensure that the mean time between failures of the device is more than 100000 hours.


Contact Us