RWB-400Z Microcomputer Protection Device

The digital microcomputer protection device is suitable for 35kV and below small current/small resistance grounding system, set protection, control, communication, monitoring and other functions.
The device uses the idea of component programmable design to reduce the maintenance workload and spare parts, and can flexibly meet the needs of various applications.
The device can be centrally assembled and dispersed on the switch cabinet. The communication mode is RS485 bus.

→ Download Catalog

Contact Us Category Digital Protection Relay
  • Product Details
  • Main function configuration
  • Technical parameter
  • Main feature
The digital microcomputer protection device is suitable for 35kV and below small current/small resistance grounding system, set protection, control, communication, monitoring and other functions.
The device uses the idea of component programmable design to reduce the maintenance workload and spare parts, and can flexibly meet the needs of various applications.
The device can be centrally assembled and dispersed on the switch cabinet. The communication mode is RS485 bus.

1, three phase phase current protection component

2,three-stage zero-sequence current protection component (independent tripping or alarm)

3, two-stage low zero sequence current protection component (can be independent tripping or alarm, can be used for unbalanced current protection of capacitors)

4, acceleration protection component (phase current and zero sequence current)

5, inverse-time protection component (phase current, high zero sequence current and low zero sequence current)

6, overload component (alarm and trip, can be set independently)

7 ,reclosing component

8, low frequency protection component

9, low voltage protection component

10,overvoltage protection component

11, zero sequence overvoltage protection component

12,No voltage protection component

13,Motor start fast break protection component

14,Negative sequence overcurrent component

15, overheat protection component

16,locked-rotor protection component

17,Long start protection component

18,non-electrical protection component (6 channels, can input trip or alarm, used as ordinary signal when exiting)

19, PT break detection (alarm or trip possible)

20,CT break detection (alarm or trip possible)

21,Control loop disconnection monitoring

Environmental condition

Normal temperature-10℃~55℃

Limiting temperature-30℃~70℃

Storage temperature-40℃~85℃

Rated data

Device power supply:AC/DC 110/220V or DC24V/48V (Order indication)

State quantity level: The device comes with 24VDC inside and is passively opened outside

Operating power supply:DC220VAC220VDC110VDC48V (Order indication)

    Rated AC data

a) Line voltage            100 V or 380V (Order indication)

bAlternating current   5A or 1A (Order indication)

c) Rated frequency       50Hz

Power consumption

a) DC circuit    Normal operation: no more than 10W

   Action: No more than 15W

b) AC voltage loop    Not more than 0.5VA per phase

c) AC current loop The rated current is 5A:Not more than 1VA per phase

The rated current is 1A:Not more than 0.5VA per phase

Main performance technology

4.1 Precise working range of sampling loop

        voltage0.005~1.2Un

        current0.08In~20In

4.2 Precision of various components

         current element  <±2.5%

         voltage element  <±2.5%

        time element: When 0s~2s, the error is not more than ±40ms;
        When more than 2s, the error is not more than ±3%;

Overload capacity

AC current loop 2 times the rated current continuous operation

10 times the rated current allow to work 10s

40 times the rated current allow to work 1s

AC voltage loop 1.2 times the rated current continuous operation

Power supply circuit 80%~110% rated voltage continuous operation

The device adopts a new generation of high-performance 32-bit CPU, so that the stability and computing speed of the product are fully guaranteed.

☆ The acquisition module adopts 16-bit A/D converter, and the measurement and calculation indexes can easily meet the requirements.

☆ A large-capacity storage module can record up to 32 wave recording reports, recording at least 1000 events, and maintaining power failure.

☆ The high precision clock chip ensures the accuracy of the clock when the device loses power.

☆ Careful electrical design, the whole machine has no adjustable devices, to realize the concept of debugging.

☆ High-grade, high-quality components selection.

☆ Complete self-diagnosis function.

☆  Case design with moisture, dust and vibration resistance. 

Contact Us